Specifications – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 71

Advertising
background image

PowerMonitor 1000 Unit 71

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Specifications

Parameter

Accuracy in % of Reading at 25 °C (77 °F) 50/60 Hz Unity Power
Factor

Nominal / Range

Applies to

TR1

TR2

EM1

EM2

EM3

Voltage Sense

Inputs: V1, V2, V3

±0.5%

X

X

X

Line-neutral rms:

347V / 15…399V

Line-line rms:

600V / 26…691V

Current Sense

Input: I1, I2, I3

±0.5%

X

X

X

5A / 0.05…10.0 A rms

Frequency

±0.05 Hz

X

X

X

50 or 60 Hz /

40…75 Hz

Power Functions:

kW, kVA, kVAR

EN62053-21:2003

Accuracy

Requirement Class

1

(1)

(1) Fast transient external influence tested at 2 kV.

X

X

Demand Functions:

kW, kVA

X

X

Energy Functions:

kWH, kVAH

kWh

only

X

X

Metering Update

Rates

100 ms V, I, Hz

200 ms Power

X

X

X

X

X