Parameter

Description

Range

Default

User
Setting

Demand

Source

(advanced

setup)

Selects the source of the demand end-of-interval (EOI) signal.
0 = Internal Timer

1 = Status Input 2

2 = Controller Command

3 = Ethernet Demand Broadcast

Network-demand synch options are available only on units with an

optional Ethernet network installed.

If Demand Broadcast Master Select is set to master then a Demand
Source value of 0…2 selects the EOI source that is used to trigger the
demand-synch master broadcast.

If Demand Broadcast Master Select is set to slave then a Demand
Source value of 0…3 selects the EOI source.

0…3

0

Demand

Period

Length

(advanced

setup)

Specifies the period for demand calculations. The following include

special cases.
Demand source = 0 (internal time) and demand period length = 0 then

demand metering is disabled
Demand source 0 and demand period length = 0 then projected demand

is disabled
Demand source 0 and demand period length 0 then projected demand is

calculated using the unit’s internal clock

0…

99 min

15 min

Number of

Demand

Periods

(advanced

setup)

Specifies the number of demand periods to average together for demand

measurement. This parameter is used for sliding window demand

calculations. For example, for a 30 minute sliding-window, demand

period length = 2 minutes and number of demand periods = 15.

1…15

1

Forced

Demand Sync

Delay

(advanced

setup)

If demand source 0 and demand period length 0 then this parameter

determines how long the unit waits for an EOI pulse, command, or

broadcast after the expected control pulse has not been received. If the

EOI signal is not received before the waiting period expires, a new

demand period starts and a record is entered in the status log.
Special case: 0 = Wait forever

0…900 s

10

Demand

Broadcast

Master Select

(Ethernet

setup)

0 = Slave, the unit uses its selected demand source to calculate demand.

If demand source = 3 (Ethernet demand broadcast) the unit will listen to

the selected-broadcast port number for a broadcast from the

demand-sync master unit.
1 = Master, the unit broadcasts an EOI broadcast to the selected-UDP

port number when the selected demand source detects an EOI event.

0…1

0

Broadcast

Port Number

(Ethernet

setup)

Specifies the listening or broadcast port for the UDP Ethernet-demand

broadcast message.

300…

400

300