Status log, I/o functions – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 63

Advertising
background image

PowerMonitor 1000 Unit 63

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Status Log

The Status log records the date and time of changes made to the device and of external events.

The status log consists of 50 records and operates in a circular or FIFO fashion. The status log

may not be cleared.
This function applies to all models.

Logged Events

Configuration changed

Clock set

Relay output forced on or off

Status input activated or deactivated (may be disabled)

Status input counter 1 or 2 rollover or set

Missed external sync pulse

Energy register rollover or set

Device power-up or power-down

Self-test status

Results

Status log records can be accessed only via communication.

Related Functions

Log status input changes

I/O Functions

The I/O functions include

Relay KYZ Output

,

Status Inputs

, and

Configuration Lock Input

.

Relay KYZ Output

The KYZ output is a solid-state relay designed for low-power, long-life signaling operation. Its

typical use is to provide a pulse output proportional to energy consumption to an external

totalizer.
This function applies to catalog numbers 1408-EM1, 1408-EM2, and 1408-EM3 for energy

pulse.
This function applies to all models for forced operation.