Ethernet, Communication, Ethernet communication – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 23: Rs-485 multi-drop typical wiring

Advertising
background image

PowerMonitor 1000 Unit 23

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

RS-485 Multi-drop Typical Wiring

Ethernet Communication

The power monitor with optional Ethernet network communication connects easily to

industry-standard Ethernet hubs and switches using standard UTP (unshielded twisted-pair)

cables with RJ-45 connectors.

Terminal

Signal

Function

1

TX+

Transmit + (TX+)

2

TX-

Transmit - (TX-)

3

RX+

Receive + (RX+)

4

5

6

RX-

Receive - (RX-)

7

8

24V DC (by user)

RS-485

+

-

SHLD

+

-

SHLD

+

-

SHLD

+

-

SHLD

*

*

PowerMonitor 1000

* 150

Ω Terminating Resistor (if used)

PowerMonitor 1000

PowerMonitor 1000

PowerMonitor 1000

RS-485

RS-485

RS-485

Nine-pin Null Modem Cable
(Female/Female)
To Computer

2

RS-485 Wiring:
2/C Shielded Cable 0.32…4 mm (22…14 AWG)
Connect A on converter to - on each PowerMonitor 1000.
Connect B on converter to + on each PowerMonitor 1000.
Connect shield at one end only of each link.
Maximum cable length 1219 m (4000 ft.).

RS-485 to RS-232 Converter

Examples:
Allen-Bradley 1761-NET-AIC (shown)
B&B Electronics 485SD9TB

TERM

A

B

COM

SHLD

CHS GND

CHS GND

RS-232

24V DC

DC NEUT

GRND

Advertising