52 PowerMonitor 1000 Unit

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Voltage, Current, and Frequency Metering

This function applies to catalog numbers 1408-TR1, 1408-TR2, and 1408-EM3.

Metered Parameters

The power monitor calculates and returns voltage, current, and frequency measurements

including these:

L1, L2, L3, and Average Current, A

L1-N, L2-N, L3-N, and Average L-N Voltage, V

L1-L2, L2-L3, L3-L1, and Average L-L Voltage, V

Frequency

Percent Current Unbalance

Percent Voltage Unbalance

Line-to-neutral voltage results are not provided for Delta and Open Delta wiring modes.
Voltage and current unbalance are calculated according to the following formula.

Setup

Only basic analog-input setup is required for power metering.

Results

Voltage, current, and frequency metering results may be viewed using the following methods:

Web interface

LCD screen

Communication

HyperTerminal communication tool

Related Functions

Metering result averaging

Configuration lock

Maximum Deviation from Average