Operation, Setup, Commands – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 64: Related functions

Advertising
background image

64 PowerMonitor 1000 Unit

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Operation

The KYZ output can operate in any of the following modes:

Energy pulse operation with fixed pulse width or toggle

Forced operation

Setup

KYZ-output set-up parameters are found in the Advanced Setup menu and are summarized in

the table.

Commands

Force KYZ Output On

Force KYZ Output Off

Remove Force from KYZ

Related Functions

Configuration lock

Parameter

Description

Range

Default

User
Setting

Model

TR
1

TR
2

E
M
1

E
M
2

E
M
3

KYZ Output

Parameter

0 = Disable

1 = Wh Fwd

2 = Wh Rev

0…2

0

• • •

3 = VARh Fwd

4 = VARh Rev

5 = VAh

0…5

• •

KYZ Output Scale The increase in value of the

selected parameter that caused

the output to change state

1…

100,000

1000

• • •

KYZ Pulse

Duration Setting

0 = toggle output

50…1000 = duration of output

pulse, rounded to 10 ms

0 or 50…

1000

250 ms

• • •

Advertising