Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 72

Advertising
background image

72 PowerMonitor 1000 Unit

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Parameter

Rating

Control Power

85…264V AC 47…63 Hz
125…250V DC
4 VA max

Voltage Sense Inputs: V1, V2, V3

Input impedance: 5 M  min
Input current: 2 mA max

Current Sense Inputs: I1, I2, I3

Overload withstand:

15 A continuous, 200 A for 1/2 s

Burden: 0.05V A

Impedance: 0.002 

Max crest factor at 5 A is 3.0

Starting current: 5 mA

Status Inputs

Contact closure (internal 24V DC)

KYZ Output

80 mA at 240V AC / 300V DC

Attribute

Value

Dielectric withstand

Control power

2500V

Voltage inputs

2500V

Current inputs

2500V

Status inputs

2500V

KYZ output

2500V

Terminal blocks

0.34…2.5 mm

2

(22…14 AWG), 75 °C (167 °F) min, copper wire only

Recommended torque 0.8 N•m (7 lb•in)

Operating

temperature

-10…60 °C (14…140 °F)

Storage temperature

-40…85 °C (-40…185 °F)