PowerMonitor 1000 Unit 65

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Status Inputs

The power monitor has two self-powered (24V DC) status inputs. Two typical uses for status

inputs are to totalize external pulse meters and to synchronize the demand end of interval (EOI).
This function applies to catalog numbers 1408-EM1 (except demand EOI synch), 1408-EM2,

and 1408-EM3.

Operation

Each time status input 1 sees an off-to-on transition, the status input 1 scale factor is added to the

status input 1 count. The count continues to increase, rolling over to zero at a value of
9,999,999,999,999 (10

12

– 1). Status input 2 operates in the same fashion. Status input 2

counter operates whether or not the input is used for demand EOI synchronization.

Setup

The set-up parameters for pulse totalizing and scaling are in the Advanced Setup menu and are

summarized in this table.

Setup for demand EOI synchronization is described in the

Demand Metering

section.

Metering Parameters

Status 1 Count x1,000,000 and x1

Status 2 Count x1,000,000 and x1

Commands

The following commands may be used to preset or reset the status input counters:

Set Status 1 Count

Set Status 2 Count

Parameter

Description

Range

Default

User
Setting

Model

TR1

TR2

EM1

EM2

EM3

Status Input 1

Input Scale

When a status input

sees an off to on

transition, the status

input count is

increased by the scale

factor.

1…

1,000,000

1

Status Input 2

Input Scale

1…

1,000,000

1