PowerMonitor 1000 Unit 39

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Set-up Menus

Whichever set-up method you select, set-up parameters are organized in five set-up menus.

Analog input setup

Advanced setup

RS-485 communication setup

Optional Ethernet network communication setup

Date and time setup

Features

This section describes in detail the functions of the power monitor. Each function includes

information on set-up menus and parameters used to control its operation.

Analog Input Setup

This feature applies to all models.

Setup

The power monitor calculates metering results based on scaled voltage and current inputs.

Setting up the analog inputs is necessary to obtain accurate, properly scaled metering results.

Parameter

Description

Range

Default

User
Setting

Voltage mode

Should match the external electrical system and

how it is wired to the PowerMonitor voltage and

current input terminals. Refer to the wiring

diagrams.
0 = Direct Delta

1 = Open Delta

2 = Wye

3 = Single Phase

4 = Demo, simulated results

5 = 1PT1CT-LL

6 = 1PT1CT-LN

0…4

2

PT primary

The primary value of the PT ratio (Pri:Sec) indicating

the nominal voltage present at the high-end of the

transformer. For direct connect, set the PT ratio to

any valid 1:1 ratio (for example, 480:480).

1.00… 50,000

480