Miscellaneous functions – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 67

Advertising
background image

PowerMonitor 1000 Unit 67

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

Miscellaneous Functions

The power monitor includes a small number of miscellaneous functions that you can select.

Set-up parameters of these functions are in the Advanced Configuration set-up menu.

Parameter

Description

Range

Default

User
Setting

New Password

Select a new password if desired to help prevent

unauthorized changes to the unit setup.

0…9999

0

Metering Result

Averaging

If enabled, metering results are averaged by using the

previous eight cycles to smooth the results.

0 = Off

1 = On

1

Log Status Input

Changes

(1)

(1) Log status input changes parameter is not accessible from the LCD screen.

If disabled, prevents routine status input changes from

filling up the status log. Useful when a status input is used

for pulse counting or demand EOI synch.

0 = Disable

1 = Enable

0

Unit Error Action

Determines the unit’s response to a hardware or firmware

error.
0 = Halt, make status indicator solid red

1 = Reset the unit

0…1

1

Software Error Log

Full Action

Determines the unit response when a firmware failure is

detected and the error log is full.
0 = Halt on error and wait for clear log command, make

status indicator solid red

1 = Perform a firmware reset

0…1

1

Advertising