Kyz output, Control power, Connect communication – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 20

Advertising
background image

20 PowerMonitor 1000 Unit

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

KYZ Output

The KYZ solid-state relay output may be connected to an external pulse accumulator or

controller. Wetting voltage must be provided by the external device or circuit. The KYZ output

is designed for low-current (80 mA maximum) switching at up to 240V AC or 300V DC. The

diagram indicates typical KYZ wiring.

KYZ Output

Control Power

Connect the power monitor to a source of 120/240V AC or 125…250V DC control power

through a user-provided disconnecting means. Provide overcurrent protection sized to protect

the wiring. The power monitor is internally protected. Apply control power only after all wiring

connections are made to the unit.

Control Power

Connect Communication

The following sections provide information on connecting

Serial Communication

and

Ethernet

Communication

to the power monitor.

PowerMonitor 1000 Unit

(equivalent circuit)

Wetting Power

Supply

240V AC or 300V DC

(by user)

Pulse Accumulator

or Controller

(by user)

( + )

( - )

IN1

COM

(N.C.)

Z

(COM)

(N.O.)

K

Y

120/240V AC or

125…250V DC

50/60 Hz

4V A Max.

Ground

L1

L2

*

*

* You provide.