Magnitude and Phase Angle

The power monitor continually returns voltage and current magnitude and phase angle data.

This data may be used to construct a phasor diagram, and in addition to the diagnostics

parameters, to troubleshoot wiring issues. The following exceptions apply.

Magnitude data is not returned by models 1408-EM1 and -EM2

Current phase angle 2 always returns 0 in open-delta wiring mode

Phase angles are consistent with the four-quadrant power metering diagram.

Refer to Power Metering on page 50

.

Setup

Basic analog setup is required. In addition, a system power factor should be selected. The ranges

are as follows:

Low (52…95% lag, default setting)

High (85 lag …98% lead)

Leading (97 lag …89% lead)

Results

Wiring diagnostics results may be viewed using the following methods:

Web interface

LCD screen

Communication

HyperTerminal communication tool

Commands

Perform wiring diagnostics

Test wiring connections (LCD screen menu)

TIP

The Troubleshooting mode of the power monitor lets you view magnitude data.

Please refer to

Troubleshooting Mode

on

page 43

.