Status inputs, 1pt and 1ct line-to-neutral, Status inputs (s1, s2) – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 19

Advertising
background image

PowerMonitor 1000 Unit 19

Rockwell Automation Publication 1408-IN001E-EN-P - September 2013

1PT and 1CT Line-to-Neutral

Status Inputs

One or two dry (non-powered) contacts can be connected to the power monitor status inputs.

The power monitor 24V DC status input derives power from its internal power supply.
Connect status inputs by using shielded, twisted-pair cable with the shield connected to the

ground bus or other low-impedance earth ground at one end only. The diagram indicates typical

status input wiring.

Status Inputs (S1, S2)

V1

L1

L2

L3

V2

VN

V3

Load

Line

Connect to ground
ONLY if PT is used

Voltage Mode = 1PT1CT Line-to-neutral

PowerMonitor 1000

Fuses

(by user)

PT

(by user,

if used)

CT

(by user)

Shorting terminal

block (by user)

I1+

I2+

I1-

I2-

Ground

Contact 1

Contact 2

Ground

SCOM

S2

S1