Installing the SLC to SCANport Module

Publication 1203–5.9 –– October 1996

To install the SLC to SCANport module into the chassis:

1. Set the DIP switches. For each SCANport device connected to

the SLC to SCANport module, you need to set two DIP switches
to select what happens when the SLC processor or rack adapter
faults or is placed in program for the appropriate channel.

Set this DIP switch:

To these settings:

To:

Channel 1 Fault/

O

1 2 3 4 5 6 7 8

SW1

SW2

Open

Open

(Off)

(Off)

Fault SCANport device
(default)

Program State
(Switches 1 and 2)

O

1 2 3 4 5 6 7 8

SW1

SW2

Closed Open
(On)

(Off)

Zero data

2

3

4

5

6

7

8

OPEN

O

1 2 3 4 5 6 7 8

SW1

SW2

Open

Closed

(Off)

(On)

Hold last state

1

2

3

O

1 2 3 4 5 6 7 8

SW1

SW2

Closed Closed
(On)

(On)

Safe state data (enhanced mode
only), Fault (basic mode only)

Channel 2 Fault/

O

1 2 3 4 5 6 7 8

SW3

SW4

Open

Open

(Off)

(Off)

Fault SCANport device
(default)

Program State
(Switches 3 and 4)

O

1 2 3 4 5 6 7 8

SW3

SW4

Closed Open
(On)

(Off)

Zero data

2

3

4

5

6

7

8

OPEN

O

1 2 3 4 5 6 7 8

SW3

SW4

Open

Closed

(Off)

(On)

Hold last state

1

2

3

O

1 2 3 4 5 6 7 8

SW3

SW4

Closed Closed
(On)

(On)

Safe state data (enhanced mode
only), Fault (basic mode only)

Channel 3 Fault/

O

1 2 3 4 5 6 7 8

SW5

SW6

Open

Open

(Off)

(Off)

Fault SCANport device
(default)

Program State
(Switches 5 and 6)

O

1 2 3 4 5 6 7 8

SW5

SW6

Closed Open
(On)

(Off)

Zero data

2

3

4

5

6

7

8

OPEN

O

1 2 3 4 5 6 7 8

SW5

SW6

Open

Closed

(Off)

(On)

Hold last state

1

2

3

O

1 2 3 4 5 6 7 8

SW5

SW6

Closed Closed
(On)

(On)

Safe state data (enhanced mode
only), Fault (basic mode only)

Installing the SLC to
SCANport Module

1

2

Switch 1 = Open (Off)
Switch 2 = Closed (On)

O
N

O

F
F