SCANport Messaging

B–27

Publication 1203–5.9 –– October 1996

Read Parameter Link from Parameter Number

The Read Parameter Link from Parameter Number message lets you
request the parameter link information for a specific parameter. The
following is an example of this request:

Service=Get Attribute Single

Internal A–B Vendor Specific Class

Instance=Parameter #5

Attribute=Link

Data Length=0 Bytes

M0:e.000

M0:e.001

M0:e.002

M0:e.003

M0:e.004

000e

0099

0005

0000

0000

Value

Read Parameter Link from Parameter Number 5

Service=Get Attribute Single

Internal A–B Vendor Specific Class

Instance=Parameter #5

Attribute=Link

Data Length=6 Bytes

M1:e.100

M1:e.101

M1:e.102

M1:e.103

M1:e.104

000e

0099

0005

0000

0006

Value

Response

Discard

M1:e.106

0000

Link Number

M1:e.105

0006

Discard

M1:e.107

0000

Figure B.19 shows a Read Parameter Link from Parameter Number
request. This example is a read of the link value of parameter 5 (the
parameter number is in N10:2). The link value is 6.

Figure B.19
Example of Read Parameter Link from Parameter Number

address 0 1 2 3 4 5 6 7 8 9
N10:0 000e 0099 0005 0000 0000

address 0 1 2 3 4 5 6 7 8 9
N11:0 000e 0099 0005 0000 0006 0006 0000 0000