Publication 1203–5.9 –– October 1996

The four formulas are shown here. The first two formulas are used
when descriptor bit 6 is set to 1.

Engineering Value =

(Internal Value + Offset) x Multiplier x Base

Divisor x 10

Decimal Precision

Internal Value =

Engineering Value x Divisor x 10

Decimal Precision

Multiplier x Base

– Offset

Engineering Value =

(Internal Value + Offset) x Multiplier x Base

Divisor

Internal Value =

Engineering Value x Divisor

Multiplier x Base

– Offset