3–10

Using Basic Mode

Publication 1203–5.9 –– October 1996

The following data table shows the input data read from the SLC to
SCANport module via the SLC backplane.

address 15 data 0

I:1 0000 0000 0000 0000 Drives 1 & 2 SCANport Channel Status

I:1.1 0000 0000 0000 0000 Drive 3 SCANport Channel Status

I:1.2 0000 0000 0000 0000 Drive 1 Logic Status

I:1.3 0000 0000 0000 0000 Drive 1 Feedback

I:1.4 0000 0000 0000 0000 Drive 2 Logic Status

I:1.5 0000 0000 0000 0000 Drive 2 Feedback

I:1.6 0000 0000 0000 0000 Drive 3 Logic Status

I:1.7 0000 0000 0000 0000 Drive 3 Feedback

The following data table shows the data to be sent to the SLC to
SCANport module via the SLC backplane.

address 15 data 0

O:1 0000 0000 0000 0000

Drives 1 & 2 SCANport Channel Enables

O:1.1 0000 0000 0000 0000

Drive 3 SCANport Channel Enable

O:1.2 0000 0000 0000 0000

Drive 1 Logic Command

O:1.3 0000 0000 0000 0000

Drive 1 Reference

O:1.4 0000 0000 0000 0000

Drive 2 Logic Command

O:1.5 0000 0000 0000 0000

Drive 2 Reference

O:1.6 0000 0000 0000 0000

Drive 1 Logic Command

O:1.7 0000 0000 0000 0000

Drive 1 Reference