Rockwell Automation 1203-SM1 SLC to SCANport Communication Module User Manual

Page 47

Advertising
background image

4–19

Using Enhanced Mode

Publication 1203–5.9 –– October 1996

The portion of the program shown in Figure 4.15 provides start/stop
control and a frequency reference to the 1305 drive connected to
SCANport channel 1. The user start is a normally open push button,
while the user stop is a normally closed push button.

Figure 4.15
Example of Drive 1 Control and Reference

| Drive 1 Drive 1 Drive 1 |

| User User START |

| Momentary Maintained Command |

| START NOT STOP Bit |

| Input Input |

| I:2.0 I:2.0 O:1.2 |

|–––––] [–––––––––––––––––––] [––––––––––––––––––––––––––––( )–––––|

| | 0 | 1 1 |

| |Drive 1 |Drive 1 | |

| |START |RUNNING | |

| |Command |Status | |

| |Bit |Bit | |

| | O:1.2 I:1.2 | |

| +–––] [––––––––]/[––––+ |

| 1 1 |

| Drive 1 Drive 1 |

| User STOP |

| Maintained Command |

| NOT STOP Bit |

| Input |

| I:2.0 O:1.2 |

|–––––]/[––––––––––––––––––––––––––––––––––––––––––––––––––( )–––––|

| | 1 | 0 |

| |Drive 1 |Drive 1 | |

| |STOP |RUNNING | |

| |Command |Status | |

| |Bit |Bit | |

| | O:1.2 I:1.2 | |

| +–––] [––––––––] [––––+ |

| 0 1 |

| Drive 1 |

| Frequency |

| Reference |

| +MOV–––––––––––––––+ |

|–––––––––––––––––––––––––––––––––––––––––––––|MOVE +–|

| |Source N20:0| |

| | 0| |

| |Dest O:1.3| |

| | 0| |

| +––––––––––––––––––+ |