3–6

Using Basic Mode

Publication 1203–5.9 –– October 1996

Channel Command Output Image Definitions

The Output Image Channel Command bits are defined as follows:

Not Used

Not Used

Not Used

Channel 2 Command

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

DE

2

DE

1

DE

3

Word 0

Word 1

Channel 1 Command

Channel 3 Command

These bits have the following definitions:

DE1
DE2
DE3

SCANport Channel 1, 2, or 3 Data Enable bit. While low (0),
the channel will not transfer I/O data between the module and
the connected SCANport device. When high (1), the channel
becomes active to the SCANport device and transfers the
appropriate I/O data. When reset to low (0), the channel
disconnects from the SCANport device. This usually causes
the connected SCANport device to fault.

This section contains an example program that uses basic mode data
transfer. The following portion of the program enables all three
SCANport channels on the SLC to SCANport module.

Figure 3.6
Example of Enabling the SCANport Channels

| Channel 1 |

| SCANport |

| Enable |

| O:1.0 |

|––––––––––––––––––––––––––––––––––––––––––––––––––––––( )––––––|

| | 0 | |

| |Channel 2 | |

| |SCANport | |

| |Enable | |

| | O:1.0 | |

| +–––( )––––| |

| | 8 | |

| |Channel 3 | |

| |SCANport | |

| |Enable | |

| | O:1.1 | |

| +–––( )––––+ |

| 0 |

Example of Basic Mode
Data Transfer