Released, Input power wires – Rockwell Automation 1398-PDM-xxx ULTRA Plus Series Positioning Drive Module User Manual

Page 67

Advertising
background image

Publication 1398-5.1 — January 2000

Wire the ULTRA Plus PDM Components 3-3

Figure 3.2
Power Wiring for 1398-PDM-75

2

7

7

11

11

4

5

5

10

11

9

9

9

9

1

3

7

5

4

3

2

1

10

A

B

C

D

PIN

SIGNAL

R

S

T

MOTOR CASE

9

1

3

10

FUSES ARE RECOMMENDED. FUSE SIZES MUST BE SELECTED
ACCORDING TO LOCAL REGULATIONS.

FUSE

BLOCK

COMMON GROUNDING

POINT FOR AMPLIFIER

SYSTEM (ONE PER AXIS)

MACHINE COMMON

GROUNDING BUS BAR

AC LINE

FILTER

AC LINE

FILTER

TO PROTECTIVE

EARTH TERMINAL

DC BUS

TB2

L2/N AUX

L1 AUX

L2/N

L3

L1

DC-

DC+

R

S

T

TERM

BLOCK

DRIVE

ALL

DM/PDM-75

L1,L2/N,

L3

L2 OR L2/AUX, ONLY L1 MAY BE SWITCHED OR FUSED.

NOTE: POWER INITIALIZATION REQUIRES A SHORT PERIOD OF INRUSH

CURRENT OF 50A FOR THE MAIN INPUT AND 95A FOR THE
AUXILIARY INPUT. DUAL ELEMENT TIME DELAY (SLOW BLOW)

21871

__

__

__

__

H-SERIES

H-SERIES

F-SERIES

F-SERIES

N-SERIES

N-SERIES

MOTORS

MOTORS

DC BUS

TB2

TB1

TB1

FUSE

BLOCK

COMMON GROUNDING

POINT FOR AMPLIFIER

SYSTEM (ONE PER AXIS)

L2/N AUX

L1 AUX

L2/N

L3

L1

DC-

DC+

R

S

T

WIRE SIZES ARE MINIMUM RECOMMENDED VALUES. THE REQUIREMENTS OF LOCAL REGULATIONS SHOULD BE OBSERVED.

TERMINATE THE MOTOR POWER CABLE SHIELD BY CLAMPING IT TO THE DRIVE WITH THE BRACKET PROVIDED. THIS BRACKET CAN BE USED FOR STRAIN RELIEF IF

AC LINE FILTER AND SHIELDED MOTOR CABLE ARE TO BE USED FOR IMPROVING THE DRIVE MODULES ELECTROMAGNETIC COMPATABILITY, AND ARE REQUIRED TO MEET THE

EUROPEAN ELECTROMAGNETIC COMPATABILITY DIRECTIVE. CAUTION: AC LINE FILTERS HAVE LARGE LEAKAGE CURRENTS AND REQUIRE DISCHARGE TIME UPON POWER REMOVAL.

NON-SHIELDED CABLES ARE USED. SNUG BRACKET SCREWS, DO NOT OVERTIGHTEN. NEVER TORQUE OVER 10 LB-IN. THE SHIELDS ON SHIELDED POWER CABLES MUST
BE GROUNDED AT A MINIMUM OF ONE POINT FOR SAFETY.

THE AUX INPUT HAS AN INTERNAL FILTER. WIRING BETWEEN THE DRIVE MODULE AND FILTER SHOULD BE KEPT AS SHORT AS POSSIBLE. THE COMMON GROUND BUS BAR SHOULD
BE AS CLOSE TO THE DRIVE AS POSSIBLE.

10 AWG/2.5mmÉ

MULTIPLE DRIVE MODULES MAY BE POWERED FROM ONE TRANSFORMER OR OTHER AC SUPPLY SOURCE.

8.

MOTOR POWER
CONNECTOR MATING

CONNECTOR

MOTOR POWER

DRIVE MODULE

TERMINAL(S)

L2/N AUX

L1 AUX,

RECOMMENDED

POWER WIRE

(GAUGE/mmÉ)

(60˚C COPPER MIN)

16 AWG/1.5mmÉ

AC AUXILIARY

(OPTIONAL)

POWER INPUT

INPUT POWER WIRES

DRIVE ENABLE INPUT MUST BE OPENED WHEN MAIN POWER IS REMOVED AND AUXILIARY POWER IS PRESENT, OR A DRIVE FAULT WILL OCCUR.

DO NOT DAISY CHAIN DRIVE MODULE POWER CONNECTIONS. MAKE SEPARATE CONNECTIONS DIRECTLY TO THE AC SUPPLY.

DRIVE RATED 100-240 VAC RMS, SINGLE OR THREE PHASE INPUT VOLTAGE (230 VAC STANDARD).

6.

CURRENT RATINGS ARE INDEPENDENT OF THE INPUT VOLTAGE. REDUCED VOLTAGE WILL RESULT IN A REDUCTION IN SPEED, BUT NOT TORQUE. DRIVE RATED 35/75 AMPS FOR
THREE PHASE INPUT, 15/50 AMPS FOR SINGLE PHASE INPUT.

A SUPPLY DISCONNECTING DEVICE IS REQUIRED FOR MAINTAINANCE & SAFETY. LOCAL REGULATIONS SHOULD BE OBSERVED. IF A GROUNDED NEUTRAL IS USED INSTEAD OF

MAY BE USED TO KEEP LOGIC SECTION OF DRIVE MODULE SUPPLIES POWERED AFTER MAIN MOTOR SUPPLY IS TURNED OFF AT L1, L2/N, L3 TERMINALS (EXAMPLE: TO RETAIN

JUMPER INSTALLED AT FACTORY FOR INTERNAL SHUNT. SEE DRAWING 9101-1328 FOR TERMINAL WIRING OF EXTERNAL SHUNT OPTION TERMINALS.

DIAGNOSTIC STATUS OF DRIVE MODULE AFTER L1, L2/N, L3 POWER DOWN).

(60˚C COPPER MIN)

H-6100

H-4050

H-4075

28.0 Amps at 100-240 Volts AC Single Phase

28.0 Amps at 100-240 Volts AC Three Phase

1.0 Amps AC at 115 Volts AC
0.5 Amps AC at 230 Volts AC

DRIVE MODULE INPUT CURRENT REQUIREMENTS

CURRENT REQUIREMENT, MAXIMUM (AMPS AC RMS)

BRU/IQ TERMINALS

L1,L2/N,L3

L1 AUX,L2/N AUX

DM/PDM-75
DM/PDM-75

L1,L2/N

MOTOR POWER CONNECTOR

MOTOR POWER WIRES R,S,T,GND

MINIMUM

RECOMMENDED

POWER WIRE

(GAUGE/mmÉ)

MOTOR

12 AWG/3.0mmÉ

8 AWG/10.0mmÉ

F-6100

F-4050

F-4075

H-6200

F-6200

MOTOR POWER

MATING CONNECTOR

10 AWG/6.0mmÉ

14 AWG/2.5mmÉ

CONTACT SIZE

(GAUGE/mmÉ)

L1

L2/N

L3

(OPTIONAL, NOT REQUIRED WHEN
DESIRED INPUT VOLTAGE IS
AVAILABLE DIRECTLY FROM THE
LINE)

TRANSFORMER
CHASSIS

ISOLATION OR AUTO TRANSFORMER

OR CIRCUIT BREAKER

AC LINE

THREE PHASE

50/60Hz

FUSED DISCONNECT

TORQUE ALL TERMINALS

TO 11 LB-IN.

TERMINAL STRIP

ACCEPTABLE WIRE RANGE

(GAUGE/mmÉ)

22-10 AWG/0.5-6mmÉ

DRIVE MODULE

„XCON…

„XCON…

NOTES

POWER WIRING CONNECTIONS

75A

.XXX±.010

DECIMALS.XX±.020

FRACTIONS:±1/64"

DO NOT SCALE DRAWING

ANGLES ±1ANGLES ˚

TOLERANCE ON:

FILLETS AND ROUNDS .02 R MAX

BREAK ALL EDGES .02 MAX

DIMENSIONS ARE IN INCHES

DATE

DATE

C

PART NO.

DWG SIZE

SHEET

SCALE

N/A

of

REV ECOCHKR

DATE

REVISION DESCRIPTION

BY

DESIGN ENGR

DRAWN BY

JM

UNLESS OTHERWISE SPECIFIED

9101-1453

4-19-96

1

1

JM

A

RELEASED

Advertising