Publication 1398-5.1 — January 2000

3-22 Wire the ULTRA Plus PDM Components

Figure 3.17
Typical Digital I/O wiring

P2

P1

12

11

10

9

8

7

6

5

4

3

2

1

12

13

14

11

10

9

8

7

6

5

4

3

2

1

OUTPUT LOADS: RESISTANCE IS 330 OHM MINIMUM

INPUT SWITCHES: RESISTANCE IS 3000 OHM MAXIMUM

24 VOLT COMMON

FORWARD LIMIT

REVERSE LIMIT

ENABLE

START

HOME SWITCH

HOME COMMAND

JOG REVERSE

JOG FORWARD

PAUSE

ERETURN

INTERRUPT #1

INTERRUPT #2

GENERAL PURPOSE INPUT

INPUT 13

INPUT 12

INPUT 11

INPUT 10

INPUT 9

INPUT 8

INPUT 7

INPUT 6

INPUT 5

INPUT 4

INPUT 3

INPUT 2

INPUT 1

GENERAL PURPOSE INPUT

GENERAL PURPOSE INPUT

GENERAL PURPOSE INPUT

GENERAL PURPOSE OUTPUT

GENERAL PURPOSE OUTPUT

GENERAL PURPOSE OUTPUT

PROGRAM RUNNING

AT HOME

HOME SEQUENCE COMPLETE

IN POSITION

ERROR

OUTPUT 8

OUTPUT 7

OUTPUT 6

OUTPUT 5

OUTPUT 4

OUTPUT 3

OUTPUT 2

OUTPUT 1

INPUT 16

INPUT 15

INPUT 14

+24 VDC

W4

INTERNAL 24 VDC SUPPLY

TYPICAL INPUT

3.3 K

24 VOLT COMMON

TYPICAL OUTPUT

W3

INTERNAL 24 VDC SUPPLY

INTERNAL

75mA MAX PER OUTPUT
500mA TOTAL