Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual

Page 101

Advertising
background image

Publication 1746-UM008B-EN-P - December 2006

Module Diagnostics and Troubleshooting 101

The LED Indicator Status Description table explains the function of the
channel status LED indicators while the module status LED indicator is
turned on.

The Module Status LED Indicator State table explains the function of
the module status LED indicator.

I/O error codes are reported in word S:6 of the SLC processor status
file. The characters denoted as XX represent the slot number (Hex) for
the module. The characters denoted as YY represent the 2-digit hex
code for the fault condition.

The format for the error codes in the status word (S:6) is shown in the
Error Code Format diagram on page 102.

LED Indicator Status Description

If Module
Status LED
Indicator is

And Channel
Status LED
Indicator is

Indicated Condition

Corrective Action

On

On

Channel enabled

No action required.

Flashing

Broken Input Condition
(open circuit for RTD or
resistance input, and
short circuit for RTD
inputs only)

To determine the exact
error, check the error bits
13…15 in the input image.
Check the channel
configuration word for
valid data. Make sure that
the input type is indicated
correctly in bits 0…3.
Refer to the
troubleshooting flowchart
on page 7-6 and chapter 5
for more information.

Out-of-range Condition

Channel Configuration
Error

Off

Power-Up

No action required.

Channel Not Enabled

No action required. For an
example of how to enable
a channel refer to chapter
6, Ladder Programming
Examples.

Module Status LED Indicator State

If Module
Status LED
Indicator is

Indicated Condition Corrective Action

On

Proper Operation

No action required.

Off

Module Fault

Cycle power. If condition persists, replace the
model or call your local distributor or
Allen-Bradley for assistance.