Channel Configuration, Data, and Status 75

Broken Input Selection (Bits 6 and 7)

The Bit Descriptions for Broken Input Selection table shows the
descriptions for bits 6 and 7. The broken input bit field lets you define
the state of the channel data word when an open-circuit or
short-circuit condition is detected for that channel.

An open-circuit condition occurs when the RTD or potentiometer or
its extension wire is physically separated or opened. This can happen
if the wire is cut or disconnected from the terminal block.

The short-circuit condition applies only to RTD input types. This can
happen if the RTD or its signal wires are shorted together for any
reason. The short-circuit condition does not apply to resistance ranges
since they start at 0 ohms, which can be a short-circuit condition.

Channel Data Word Resolution for 500

Ω, 1000 Ω, and 3000 Ω Resistance Inputs

Resistance Input

Type

Data Format (Bits 4 and 5)

Engineering Units x 1

Engineering Units x 10

Scaled-for-PID

Proportional

Counts (Defaults)

Ohms

Ohms

Ohms

Ohms

500

Ω 0.1

Ω / step

0.1

Ω / step

0.0305

Ω / step

0.0076

Ω / step

1000

Ω 0.1

Ω / step

0.1

Ω / step

0.0610

Ω / step

0.0153

Ω / step

3000

Ω 0.1

Ω / step

0.1

Ω / step

0.1831

Ω / step

0.0458

Ω / step

Bit Descriptions for Broken Input Selection

Binary

Value

Select

Description

00

zero

Force the channel data word to 0 during an open-circuit
condition or short-circuit condition.

01

upscale

Force the channel data word value to its full scale during
an open-circuit or short-circuit condition. The full scale
value is determined by the input type, data format, and
scaling selected.

10

downscale

Force the channel data word value to its low scale value
during an open-circuit or short-circuit condition. The low
scale value is determined by the input type, data format,
and scaling selected.

11

not used