Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual

Page 42

Advertising
background image

Publication 1746-UM008B-EN-P - December 2006

42 Install and Wire the Module

• Tighten terminal screws using a flat or cross-head screwdriver.

Each screw should be turned tight enough to immobilize the
wire’s end. Excessive tightening can strip the terminal screw.
The torque applied to each screw should not exceed 0.565 Nm
(5 in-lb) for each terminal.

• Follow system grounding and wiring guidelines found in your

SLC 500 Installation and Operation Manual, publication
1747-UM011.

RTD Connections to Terminal Block

Chl 1

Shield

Shield

Chl 0
RT D

Shield

RT D

Chl 0
Sense

Chl 1
Sense

Chl 0
Return Chl 1

Return

Shield

Chl 3

Chl 2
RT D

RT D

Chl 2
Sense Chl 3

Sense

Chl 2
Return

Chl 3
Return

Shield

Shield

Cable Shield

Cable Shield

Cable Shield

Add Jumper

RTD

Return

RTD

Return

Shield

Ch 0 RTD

Ch 0 Sense

Ch 0 Return

Return

RTD

Return

RTD

Shield

Ch 0 RTD

Ch 0 Sense

Ch 0 Return

Return

Sense

Sense

RTD

Return

RTD

Shield

Ch 0 RTD

Ch 0 Sense

Ch 0 Return

Return

Sense

Sense

Two-wire RTD Interconnection

Four-wire RTD Interconnection

Three-wire RTD Interconnection

Belden #9501 Shielded Cable

Belden #83503 or Belden #9533 Shielded Cable

Belden #83503 or Belden #9533 Shielded Cable

Leave one sensor wire open

Terminal Pin-outs

RTD