126 Configuration Worksheet for RTD/Resistance Module

2. Select a data format for the data word value.

Your selection determines how the analog input value registered
by the analog sensor will be expressed in the data word. Enter
your 2-digit binary code in bit field 4 and 5 of the channel
configuration word.

3. Determine the desired state for the channel data word if an open

or short circuit (RTD only) condition is detected for that
channel.

4. Enter the 2-digit binary code in bit field 6 and 7 of the channel

configuration word.

5. If the channel is configured for RTD inputs, determine if you

want the channel data word to read in degrees Fahrenheit (1) or
degrees Celsius (0) and enter a one or a zero in bit 8 of the
configuration word.

IMPORTANT

Complete step 8 if you select proportional counts data format.

Bits 4 and 5

Select
Data
Format

00 = engineering units, x1: 0.1°/step, 0.1

Ω/ step and

0.01

Ω/ step (150Ω, only).

01 = engineering units, x10: 1°/step, 1

Ω/ step, (150 Ω, only).

10 = scaled-for-PID (0 to 16383)

11 = proportional counts (-32768 to +32767) (Refer to select
scaling bits 13 and 14).

Bits 6 and 7

Select
Broken
Input
State

00 = zero

01 = upscale

10 = downscale

11 = invalid

Bits 8

Select
Temperat
ure Units

0 = degrees Celsius

1 = degrees Fahrenheit