Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual

Page 45

Advertising
background image

Publication 1746-UM008B-EN-P - December 2006

Install and Wire the Module 45

Three-wire Potentiometer Connections To Terminal Block

Cable Shield

RTD

Shield

Chl 0 RTD

Chl 0 Sense

Chl 0 Return

Return

Belden #83503 or Belden #9533 Shielded Cable

Potentiometer

Run RTD and sense wires from module to potentiometer
terminal and tie them to one point.

Potentiometer wiper arm can be connected to either the RTD or return terminal
depending on whether the user wants increasing or decreasing resistance.

Cable Shield

Run RTD and sense wires from module to potentiometer
terminal and tie them to one point.

Potentiometer

Shield

Chl 0 RTD

Chl 0 Sense

Chl 0 Return

RTD

Return

Sense

Sense

Belden #83503 or Belden #9533 Shielded Cable