Input specifications t – Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual

Page 118

Advertising
background image

Publication 1746-UM008B-EN-P - December 2006

118 Specifications

Physical Specifications

LED indicators

5 green status indicators, one for each of 4
channels and one for module status

Module ID code

3513

Max termination wire size

Two 2.5 mm

2

(14 AWG) wire per terminal

Max cable impedance

25

Ω max impedance for three-wire RTD

configuration (see Cable Specifications)

Terminal block

Removable, Allen-Bradley spare part
Catalog Number 1746-RT25G

Module Environmental Specifications

Temperature, operating

0…60 °C (32…140 °F)

Temperature, storage

-40…85 °C (-40…185 °F)

Relative humidity

5% … 95% (without condensation)

Hazardous environment classification

Class I, Division 2 Hazardous Environment

Agency certification
(when product or packaging is marked)

• UL and CSA Class I, Division 2 Groups A,

B, C, D certified

• CE compliant for all applicable

directives

Input Specifications

RTD types

Platinum, nickel, nickel iron, copper

Temperature scale (selectable)

°C or °F and 0.1 °C or 0.1 °F

Resistance scale (selectable)

1

Ω or 0.1 Ω for all resistance ranges;

or 0.1

Ω or 0.01 Ω for 150 Ω potentiometer.

Input step response

See channel step response, page 54.

Input resolution and repeatability

See RTD and resistance device
compatibility tables on page 13.

Display resolution

See Channel Data Word Resolution table on
page 74.

Module update time

See chapter 4, Update Time, page 58.

Channel turn-on time

Requires up to one module update time plus
one of the following:

• 250 Hz Filter = 388 ms
• 60 Hz Filter = 1,300 ms
• 50 Hz Filter = 1,540 ms
• 10 Hz Filter = 7,300 ms

Advertising