Appendix

C

Configuration Worksheet
for RTD/Resistance Module

The following configuration procedure and worksheet are provided to
help you configure each of the channels on your RTD module. The
channel configuration word consists of bit fields, the settings of which
determine how the channel will operate. This procedure looks at each
bit field separately and helps you configure a channel for operation.

Refer to the Channel Configuration Word (O:e.0 through O:e.3) - Bit
Definitions
table and the detailed configuration information in
Chapter 5 as needed to complete the procedures in this appendix. Or
you may prefer to use the summary worksheet on page 128.

Channel Configuration
Procedure

Proceed as follows.

1. Determine the input device type (RTD type or resistance input)

for a channel and enter its respective 4-digit binary code in bit
field 0…3 of the channel configuration word.

Bits 0-3

RTD Sensors/Setting

Resistance

Input/Setting

Platinum

(

= 0.00385)

Platinum
(

= 0.003916)

Copper
(

= 0.00426)

Nickel
(

= 0.00618)

(

= 0.00672)

Nickel Iron
(

= 0.00518)

Select
Input Type

100

Ω

0000

100

Ω

0100

10

Ω

(1)

1000

120

Ω 1001

604

Ω 1011

150

Ω

1100

200

Ω

0001

200

Ω

0101

-

-

120

Ω

(2)

1010

-

-

500 Ω

1101

500

Ω

0010

500

Ω

0110

-

-

-

-

-

-

1000

Ω

1110

1000

Ω 0011

1000

Ω 0111

-

-

-

-

-

-

3000

Ω

1111

(1)

Actual value at 0 °C (32 °F) is 9.042

Ω per SAMA standard RC21-4-1966.

(2)

Actual value at 0 °C (32 °F) is 100

Ω per DIN standard.