Ladder Programming Examples 95

Use the Proportional
Counts Data Format with
User-set Scaling

The RTD module can be set up to return data to the user program that
is specific to the application. Assume that you control the line speed
of a conveyor using a 1000

Ω potentiometer connected to channel 0 of

the RTD module. The line speed will vary between 3 ft/m when the
potentiometer is at 0

Ω and 50 ft/m when the potentiometer is at 1000

Ω.

Follow these procedures to configure the RTD module to return a
value between 3…50 in the data word for channel 0.

1. Set bits 0…3 of configuration word 0…1110 to select the 1000

Ω

potentiometer input type.

2. Set bits 4 and 5 of configuration word 0…11 to select

proportional counts data format.

3. Set bits 13 and 14 of configuration word 0…01 to select range 0

as the scaling range.

4. Enter 3 as the low range into N10:4.

5. Enter 50 as the high range into N10:5.

Rung 2:0

] [

COP

COPY FILE
Source

#N10:0

Dest

#O:3.0

Length

6

First Pass Bit

S:1

15

Initialize RTD module.

Rung 2:1

SCL

SCALE
Source

I:3.0

Rate [/10000]

Offset

Dest

] [

I:3.4

11

Set speed of conveyor motor

Channel 0 Status

Rung 2:2

END

Six elements are copied from the
specified source address (N10:0) to the
specified output (O:30:0). Each element
is a 16-bit integer as shown in the data
table at the bottom of the page.

The Source of this instruction is the
data word from the RTD module, which
is a number between 3…50. The Dest
in this application is an analog output
channel controlling the speed of the
conveyor motor drive. The Rate and
Offset parameters should be set per
your application. Refer to the SLC 500
Instruction Set Reference Manual,
publication 1747-RM001, or the Analog
I/O User Manual, publication
1746-UM005, for specific examples of
the SCL instruction.