Write Remaining Ladder Logic

The Channel Data Word contains the information that represents the
temperature value or resistance value of the input channel. Write the
remainder of the ladder logic program that specifies how your
RTD/resistance input data is processed for your application. In this
procedure, the addressing reflects the location of the module as slot 1.

Input Image Detail

Test Your RTD Program

1. Apply power.

The module status LED indicator and channel 0 status LED
indicator turn on.

2. Download your program to the SLC processor.

3. Make sure the controller is in Run mode.

For more information see chapter 7, Module Diagnostics and
Troubleshooting.

LED Indicator Status

Channel 1 Data Word

Channel 2 Data Word

Channel 3 Data Word

Output Image

SLC 500 Controller

Data Files

Bit 15

Bit 0

Word 1

Word 2

Word 3

Address

I:1.0

Input Image

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Channel 0 Data Word

Word 0

Word 7

(8 words)

Channel 1 Status Word

Channel 2 Status Word

Channel 3 Status Word

Channel 0 Status Word

(Variable RTD/resistance Input Data)

Address

I:1.0
I:1.1
I:1.2
I:1.3

I:1.7

0

1

2

3

INPUT

Channel LEDs

Module Status LED

MODULE STATUS

CHANNEL

RTD/resistance

STATUS