Determine the operating parameters for channel 0. In this example,
the figure shows the channel 0 configuration word defined with all
defaults (0) except for channel enable (bit 11). The addressing reflects
the location of the module as slot 1.

For details on how to configure the module for your application, refer
to chapter 4 and chapter 5.

A configuration worksheet is included on page 132 to assist you in
channel configuration.

For more information refer to chapter 5, Channel Configuration, Data,
and Status.

Output Image Detail

O:1.1

Channel 1 Configuration Word

Channel 2 Configuration Word

Channel 3 Configuration Word

Output Image

SLC 500 Controller

Data Files

Bit 15

Bit 0

Word 1

Word 2

Word 3

Address

O:1.0

Input Image

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Channel 0 Configuration Word

Word 0

Input T

ype

Select

Data Format Select

Broken Input Select

Temperature Units Select

Filter Frequency Select

C

hannel Enable

(8 words)

0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0

Default Settings

New Setting

Set this bit (11) to enable channel. Address = O:1.0/11

• 100 Platinum R TD (385)
• Engineering Units x 1 (0.1 ˚/ step)
• Broken Input (set data word to zero)
• Degrees Celsius ( ˚C)
• 10 Hz Filter Frequency
• Channel Disabled
• 2.0 mA Excitation Current
• Module Defined Scaling

O:1.2
O:1.3

User-set Lower Scale Limit Range 0

Word 4

O:1.4

User-set Upper Scale Limit Range 0

Word 5

O:1.5

Word 6

O:1.6

Word 7

O:1.7

Bit 15

Bit 0

Excitation

C

urrent Select

Scaling Select *

Not Defined

If proportional counts data format is used, then output words 4…7
can be used to define a user-set scaling range for each channel.

* Scaling Select bits apply to proportional counts mode.
Limit Scale W ords are only used if scaling select = 01

or

10 and

data format = 11.

User-set Upper Scale Limit Range 1

User-set Lower Scale Limit Range 1