102 Module Diagnostics and Troubleshooting

Error Codes

The error codes applicable to the RTD module range from 50H to
5AH. These are non-recoverable errors. For a description of the error
codes, refer to SLC 500 Instruction Set Reference Manual (Publication
1747–RM001).

Error Code Format

Channel Status LED Indicators (Green)

The channel LED indicator is used to indicate channel status and
related error information contained in the channel status word. This
includes conditions such as the following:

• Normal operation
• Channel-related configuration errors
• Broken input circuit errors such as open- or short-circuit (RTD

units only)

• Out-of-range errors

All channel errors are recoverable errors and after corrective action,
normal operation resumes.

Invalid Channel Configuration

Whenever a channel’s configuration word is improperly defined, the
channel LED indicator blinks and bit 15 of the channel status word is
set. Configuration errors occur for the following invalid combinations.

• Input type is a 10 Ω Copper RTD and the excitation current is set

for 0.5 mA, which is not allowed

• Scaling select bits 13 and 14 are set to 11, which is invalid
• Broken Input select bits 6 and 7 are set to 11, which is invalid
• Scaling select bits 13 and 14 are set to 01 or 10 and scaling limit

words=0

• Data format bits are set to 11 (proportional counts), the

scaling-select bits are set to 01 or 10 and the lower limit user-set
scale word is greater than or equal to the upper limit user-set
scale word

YY ± Error Code (Hex)

X

X

Y

Y

XX ± Chassis Slot Number (Hex)