Publication 1746-UM008B-EN-P - December 2006

Ladder Programming Examples 89

Configuration Word Setup

This example transfers configuration data and sets the channel enable
bits of all four channels with a single file copy instruction. The file
copy instruction copies four data words from an integer file you create
in the SLC controller’s memory, to the RTD module’s channel
configuration words.

Copy File Data Flow

11

12

13

14

15

0

0

1

0

0

0

0

9

10

8

1

6

7

0

0

0

1

4

5

0

0

0

1

0

1

2

3

Configures Channel For:

Bit Setting

200

Ω Platinum RTD (385)

Bit Number

Eng. Units x 10 (1 °F/ step)

Broken Input (Zero Data Word)

Degrees Fahrenheit (°F)

10 Hz Filter Frequency

Channel Enabled

2.0 mA Excitation Current

Default Scaling

Not Used

Channel Configuration Word 0

Channel Configuration Word 1

Channel Configuration Word 2

Channel Configuration Word 3

SOURCE DATA FILE

N10:0

N10:1

N10:2

N10:3

ADDRESS

Channel Output Word 0

Channel Output Word 1

Channel Output Word 3

DESTINATION DATA FILE

O:3.0

ADDRESS

Channel Output Word 2

O:3.1

O:3.2

O:3.3