General considerations – Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual

Page 37

Advertising
background image

Publication 1746-UM008B-EN-P - December 2006

Install and Wire the Module 37

General Considerations

Most applications require installation in an industrial enclosure to
reduce the effects of electrical interference. RTD inputs are susceptible
to electrical noises due to the small amplitudes of their signal.

Group your modules to minimize adverse effects from radiated
electrical noise and heat. Consider the following conditions when
selecting a slot for the RTD module. Position the module in a slot:

• away from power lines, load lines and other sources of electrical

noise such as hard-contact switches, relays, and AC motor
drives.

• away from modules which generate significant radiated heat,

such as the 32-point I/O modules.