Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual

Page 113

Advertising
background image

Publication 1746-UM008B-EN-P - December 2006

Application Examples 113

Channel Configuration Worksheet (With Settings Established)

Input Type Select

Data Format Select

Broken Input Select

Temperature Units Select

Filter Frequency Select

Channel Enable

Excitation Current Select

Scaling Select

Not Used

11

12

13

14

15

1

0

1

0

0

0

0

9

10

8

0

6

7

0

0

0

0

4

5

1

0

1

0

1

2

3

0

0

0

0

0

0

0

1

0

0

0

0

Bit Number

1

1

1

1

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

1

1

0

0

1

0

1

0

1

0

1

0

Channel 0 (Ambient)

Channel 1 (Bath)

Channel 2 (Steam)

Channel 3 (Chilled H

2

O)

Bits
0…3

Input Type Selected

0000 = 100

Ω Pt. (385)

0001 = 200

Ω Pt. (385)

0010 = 500

Ω Pt. (385)

0011 = 1000

Ω Pt. (385)

0100 = 100

Ω Pt. (3916)

0101 = 200

Ω Pt. (3916)

0110 = 500

Ω Pt. (3916)

0111 = 1000

Ω Pt. (3916)

1000 = 10

Ω Cu (426)

(1)

1001 = 120

Ω Ni (618)

(2)

1010 = 120

Ω Ni (617)

1011 = 604

Ω Ni-Fe (518)

1100 = 150

Ω Potentiometer

1001 = 500

Ω Potentiometer

1110 = 1000

Ω Potentiometer

1111 = 3000

Ω Potentiometer

Bits 4
and 5

Data Format Select

00 = engineering units, x 1

(3)

01 = engineering units, x10

(4)

10 = scaled-for-PID (0 to 16383)
11 = proportional counts (-32768 to +32767)

Bits 6
and 7

Broken Input Select 00 = zero

01 = upscale

10 = downscale

11 = invalid

Bits 8

Temperature Units
Select

0 = degrees Celsius

1 = degrees Fahrenheit

Bits 9
and 10

Filter Frequency
Select

00 = 10 Hz

01= 50 Hz

10 = 60 Hz

11 =250 Hz

Bit 11

Channel Enable

0 = channel disabled

1 = channel enabled

Bit 12

Excitation Current
Select

0 = 2.0 mA

1 = 0.5 mA

Bit 13
and 14

Scaling Select

00 = module defined scaling
(default)

01 = config. words 4 and 5
for scaling

10 = config words
6 & 7 for scaling

11 = Not used (config
error)

Bits 15

Not Used

0 = always make this setting

(1)

Actual value at 0 °C (32 °F) is 9.042

Ω per SAMA standard RC21-4-1966.

(2)

Actual value at 0 °C (32 °F) is 100

Ω per DIN standard.

(3)

Values are 0.1 °/step or 0.1

Ω /step for all resistance input types except 150 Ω. For the 150 Ω resistance input type, the values are in 0.01 Ω /step.

(4)

Values are 1 °/step or 1

Ω /step for all resistance input types except 150 Ω. For the 150 Ω resistance input type, the values are in 0.1 Ω /step.