Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual

Page 127

Advertising
background image

Publication 1746-UM008B-EN-P - December 2006

Configuration Worksheet for RTD/Resistance Module 127

6. Determine the desired input filter frequency for the channel and

enter the 2-digit binary code in bit field 9 and 10 of the channel
configuration word.

A smaller filter frequency increases the channel update time, but
also increases the noise rejection. A larger filter frequency
decreases the noise rejection, but also decreases the channel
update time.

7. If the channel will be used in your system, it must be enabled by

placing a one in bit 11 if the channel is to be enabled or a zero
in bit 11 if the channel is to be disabled.

8. Select the excitation current for the inputs.

A zero in bit 12 provides an excitation current of 2.0 mA; a 1 will
provide 0.5 mA.

9. If you have selected scaled-for-PID or proportional counts data

formats, you can choose module defined scaling (this applies
the scale associated with your data format selection in step 2).

In addition, use bits 13 and 14 if you want to define the scaling
range yourself for proportional counts data format (user-set
scaling). If you choose to define the scaling range for
proportional counts, make sure to enter the lower and upper
user-set limits in words 4 and 5 (defines range 0) or 6 and 7
(defines range 1).

Refer to Chapter 5.

10. Make sure a zero is in bit 15. This bit is not used.

Bits 9
and 10

Select Filter
Frequency

00 = 10 Hz

01 = 50 Hz

10 = 60 Hz

11 = 250 Hz

Bit 11

Channel
Enable

0 = channel disable

1 = channel enabled

Bit 12

Excitation Current

0 = excitation current = 2.0 mA
1 = excitation current - 0.5 mA

Bits 13
and 14

Select
Scaling

00 = module defined scaling

01 = configuration words 4 and 5 used for scaling (range 0)

10 = configuration words 6 and 7 used for scaling (range 1)

11 = not used (invalid setting)

Advertising