Publication 1746-UM008B-EN-P - December 2006

40 Install and Wire the Module

Terminal Wiring

The RTD module contains an 18-position, removable terminal block.
The terminal pin-out is shown in RTD Connections to Terminal Block
on page 42.

Terminal Block

NR4 Wiring Considerations

Follow the guidelines below when planning your system wiring.

Since the operating principle of the RTD module is based on the
measurement of resistance, take special care in selecting your input
cable. For 2–wire or 3–wire configuration, select a cable that has a
consistent impedance throughout its entire length.

ATTENTION

Disconnect power to the SLC before attempting to install,
remove, or wire the removable terminal wiring block.

To avoid cracking the removable terminal block, alternate the
removal of the terminal block release screws.

Cable Selection

Configuration

Recommended Cable

Two-wire

Belden #9501 or equivalent

Three-wire less than 30.48 m (100 ft)

Belden #9533 or equivalent

Three-wire greater than 30.48 m (100 ft) or
high humidity conditions

Belden #83503 or equivalent

Shield

Channel 0 RTD

Channel 0 Sense

Channel 0 Return

Shield

Channel 2 RTD

Channel 2 Sense

Channel 2 Return

Shield

Release Screw
Max. Torque =
0.6 Nm (5.3 in-bs)

Release Screw
Max. Torque =
0.6 Nm (5.3 in-bs)

Shield

Channel 1 RTD

Channel 1 Sense

Channel 1 Return

Shield

Channel 3 RTD

Channel 3 Sense

Channel 3 Return

Shield