Publication 1746-UM008B-EN-P - December 2006

92 Ladder Programming Examples

Verify Channel
Configuration Changes

When executing a dynamic channel configuration change, there is
always a delay from the time the ladder program makes the change to
the time the RTD module gives you a data word using that new
configuration information. Therefore, it is very important to verify that
a dynamic channel configuration change took effect in the RTD
module. This is particularly important if the channel being
dynamically configured is used for control. The Program to Verify
Configuration Word Data Changes ladde
r diagram explains how to
verify that channel configuration changes have taken effect.

Program to Verify Configuration Word Data Changes

EXAMPLE

Execute a dynamic configuration change to channel 2 of the
RTD module located in slot 3 of a 1746 chassis, and set an
internal data valid bit when the new configuration has taken
effect.

] [

COP

COPY FILE
Source

#N10:0

Dest

#O:3.0

Length

4

S:1

15

Set up all four channels.

Rung 2:0

Set channel 2 to display in ˚C.

] [

0

Rung 2:1

B3

0

I:1.0

[OSR]

MOVE
Source

N10:4

Dest

O:3.2

MOV

Rung 2:2

B3

1

MOVE
Source

N10:2

Dest

O:3.2

MOV

0

I:1.0

[OSR]

Set channel 2 back to display in ˚F.

]/[

Rung 2:3

MASKED MOVE
Source

I:3.6

Mask

9FFF

Dest

N7:0

MVM

BITWISE EXCLUS OR
Source A

N7:0

Mask

O:3.2

Dest

N7:1

XOR