128 co, Channel configuration worksheet – Rockwell Automation 1746-NR4 SLC RTD/Resistance Input Module User Manual User Manual

Page 128

Advertising
background image

Publication 1746-UM008B-EN-P - December 2006

128 Configuration Worksheet for RTD/Resistance Module

11. Build the channel configuration word for every channel that is

being used on each RTD module repeating the procedures given
in steps 1…10.

12. Enter the completed configuration words for each module into

the summary worksheet on the following page.

13. Following the steps outlined in Chapter 6, Ladder Programming

Examples, enter this configuration data into your ladder program
and copy it to the RTD module.

Channel Configuration Worksheet

Input Type Select

Data Format Select

Broken Input Select

Temperature Units Select

Filter Frequency Select

Channel Enable

Excitation Current Select

Scaling Select

Not Used

11

12

13

14

15

9

10

8

6

7

4

5

2

3

Bit Number

Channel 0

Channel 1

Channel 2

Channel 3

0

0

0

0

0

1

Bit Definitions

Bits
0…3

Input Type Select

0000 = 100

Ω Pt. (385)

0001 = 200

Ω Pt. (385)

0010 = 500

Ω Pt. (385)

0011 = 1000

Ω Pt. (385)

0100 = 100

Ω Pt. (3916)

0101 = 200

Ω Pt. (3916)

0110 = 500

Ω Pt. (3916)

0111 = 1000

Ω Pt. (3916)

1000 = 10

Ω Cu (427)

(1)

1001 = 120

Ω Ni (618)

(2)

1010 = 120

Ω Ni (672)

1011 = 604

Ω Ni-Fe (518)

1100 = 150

Ω

1101= 500

Ω

1110= 1000

Ω

1111= 3000

Ω

Bits 4
and 5

Data Format Select

00 = engineering units, x1

(3)

01 = engineering units, x10

(4)

10 = scaled-for-PID (0…16,383)
11 = proportional counts(-32,768…32,767)

Bits 6
and 7

Broken Input Select

00 = zero

01 = upscale

10 = downscale

11 = invalid

Bit 8

Temperature Units
Select

0 = degrees Celsius

1 = degrees Fahrenheit