Rockwell Automation Publication 1738-UM005A-EN-P - July 2013

Chapter 4 Configure the Adapter for Direct Connection in RSLogix 5000 Software

4. Choose Download for both instances.

Notice that the 1756-ENBT Bridge is now online. If yellow triangles are
present, see the following section.

Verify the Module
Chassis Size

You have now built the I/O tree in RSLogix 5000 software and the RSLogix
5000 software used the chassis size from the 1738-AENT/B adapter General tab.
Now you need to download this new chassis size value into the 1738-AENT/B
adapter hardware. This procedure will synchronize the chassis size value from the
RSLogix 5000 software into the 1738-AENT/B adapter hardware. Note that you
must be online to perform this procedure.

1. Verify that RSLogix 5000 software is online.
2. Right-click on the 1738-AENT/B adapter under I/O Configuration in

the Project window.

3. Select Properties.
4. Click the Connection tab.