Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

2. Select the appropriate filter for Module Type Category (for the example we

selected Digital) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.

3. Choose the 1738-OB4EM12 module from the list and click Create.

4. Enter these values in the New Module dialog:

Note the module definition properties on the bottom left of the New
Module dialog. You have the option to change these properties. Note that
some of the properties cannot be modified while pending edits exists.

5. Select Change...

The Module Definition dialog displays.

6. Change the Connection properties to Rack Optimization and select OK.
7. In the New Module dialog, click OK to accept the configuration.

Name

ArmorPoint Digital Output

Slot

2