Certifications – Rockwell Automation 1738-AENT, Series B ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual

Page 94

Advertising
background image

82

Rockwell Automation Publication 1738-UM005A-EN-P - July 2013

Appendix A Specifications

Certifications

1738-AENT/B EtherNet/IP Adapter modules have the following
Certifications..

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g

Emissions

CISPR 11:
Class A

ESD immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4:
±4 kV @ 2.5 kHz on power ports
±3 kV @ 5 kHz on communications ports

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communications ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Environmental Specifications

Attributes

Description

Certification (when product
is marked)

(1)

(1) See the Product Certification link at

http://www.rockwellautomation.com/products/certification/

for

Declaration of Conformity, Certificates, and other certification details.

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and

Canada. See UL File E322657.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR11; Industrial Emissions

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications