Chapter 6 Troubleshoot the Adapter

Status Indicators for 1738-AENT/B Adapter

Indicator

Status

Description

Adapter Status

Off

No power applied to device

Flashing green

Device needs commissioning due to missing, incomplete, or incorrect configuration.

Solid green

Device operating normally

Flashing red

Recoverable fault.
Complete firmware update, verify address switches.

Solid red

Unrecoverable fault has occurred:

• self test failure (checksum failure at power cycle, ramtest) at power cycle.
• firmware fatal error.

Flashing red/green

Module self-test

Network Activity

Off

No Link established.

Flashing green/Off

Transmit or receive activity present.

Solid green

Link established.

Network Status

Off

Device not initialized. The module does not have an IP address.

Flashing green

No CIP connections present. Device has an IP address, but no CIP
connections are established.

Solid green

CIP connections present. Device online and has an IP address, and CIP
connections are established.

Flashing red

One or more CIP connections in timed-out state. Check for I/O module failure
and controller operation.

Solid red

Duplicate IP address detected.
Verify IP address setting and correct, as needed.

Flashing red/green

The module is performing a self-test (only occurs during cycle
power test).

POINTBus Status

Off

Device not powered – check module status indicator.

Flashing red/green

LED cycle power test present.

Flashing red

Recoverable fault occurred:

• At cycle power, the number of expected modules does not equal the number of modules

present.

• A module is missing.

• Node fault (I/O connection timeout) occurred.

Solid red

Unrecoverable fault occurred – the adapter is bus off.

Flashing green

Firmware (NVS) update in progress.

Solid green

Adapter online with connections established (normal operation,
Run mode).

System Power

Off

Not active; field power is off or DC-DC converter problem present.

Solid green

System power is on; DC-DC converter is active (5V).

Field Power

Off

Not active; field power is off.

Solid green

Power is on; 24V is present.