Rockwell Automation Publication 1738-UM005A-EN-P - July 2013

65

Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5

The digital output module appears in the I/O configuration indented
under the 1738-AENT/B adapter.

Add the ArmorPoint Analog Modules and Configure For Direct
Connection

Analog and specialty modules must be configured for direct connection. Refer to
the following procedure to add the 1738-IE2CM12 and the 1738-OE2CM12
analog modules to the I/O configuration.

Add the Analog Current Input Module

1. Highlight the 1738-AENT/B adapter under the I/O Configuration

folder, right-click and select New Module.

The Select Module Type dialog opens.

2. Select the appropriate filter for Module Type Category (for the example we

selected Analog) and Module Type Vendor (for the example we selected
Allen-Bradley).
Note: to select only one category you will need to unselect those already
selected.