Verify the module chassis size – Rockwell Automation 1738-AENT, Series B ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual

Page 82

Advertising
background image

72

Rockwell Automation Publication 1738-UM005A-EN-P - July 2013

Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

Verify the Module
Chassis Size

You have now built the I/O tree in RSLogix 5000 software and the RSLogix
5000 software used the chassis size from the 1738-AENT/B adapter General tab.
Now you need to download this new chassis size value into the 1738-AENT/B
adapter hardware. This procedure will synchronize the chassis size value from the
RSLogix 5000 software into the 1738-AENT/B adapter hardware. Note that you
must be online to perform this procedure.

1. Verify that RSLogix 5000 software is online.
2. Right-click the 1738-AENT/B adapter under I/O Configuration in the

Project window.

3. Select Properties.
4. Click the Connection tab.

You see the Module Fault error code

5. Click the Chassis Size tab.
6. Click Set Chassis Size in Module.

Value from
RSLogix 5000 software

Value stored in
1738-AENT/B
adapter