Environmental specifications, Input specifications, Environmental specifications input specifications – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 102

Advertising
background image

Publication 1746-UM003A-EN-P

A-2 Specifications

Environmental Specifications

Input Specifications

Operating Temperature

0°C to +60°C (+32°F to +140°F)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Relative Humidity

5% to 95% (without condensation)

Hazardous Environment Classification

Class I, Division 2

Agency Certification
(when product or packaging is marked)

UL and CSA Class I,
Division 2 Groups A, B, C, D certified
CE compliant for all applicable directives

RTD Types

platinum, nickel, nickel iron, copper
(For additional information on RTD types, see page A-3.)

Temperature Scale
(Selectable)

C or F and 0.1 C or 0.1 F

Resistance Scale
(Selectable)

1

or 0.1

for all resistance ranges except 150

; or 0.1

or

0.01

for 150

potentiometer.

Input Step Response

See channel step response, page 3-5.

Input Resolution and
Repeatability

See RTD and resistance device compatibility tables on page 1-3.

Display Resolution

See Channel Data Word Resolution table on page 4-14.

Module Update Time

See Chapter 3, Update Time, page 3-10.

Channel Turn-On Time

Requires up to one module update time plus 125 milliseconds x
the number of unique input type and excitation current
combinations.

Channel Turn-Off Time

Requires up to one module update time.

Reconfiguration Time

Requires up to one module update time plus 125 milliseconds x
the number of unique input type and excitation current
combinations.

RTD Excitation Current

Two current values are user-selectable:
0.25 mA - Recommended for use with higher resistance ranges
for both RTDs and direct resistance inputs (1000

RTDs and

3000

resistance input). Refer to RTD manufacturer for

recommendations.
1.0 mA - Recommended to use for all other RTD and direct
resistance inputs, except 1000

RTDs and 3000

resistance

input ranges are limited. Refer to RTD manufacturer for
recommendations.