Resistance device compatibility, Cable specifications, Rtd standards – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 105: Cable specifications rtd standards

Advertising
background image

Publication 1746-UM003A-EN-P

Specifications A-5

Resistance Device Compatibility

Table A.1 Resistance Input Specifications

Cable Specifications

RTD Standards

Input Type

Resistance Range
(0.25 mA Excitation)

Resistance Range
(1.0 mA Excitation)

Resolution

Repeatability
(28 Hz, 50/60 Hz)

Resistance

150

0 to 150

0.01

± 0.04

500

0 to 500

0.1

± 0.2

1000

0 to 1000

0.1

± 0.2

3000

0 to 3000

0.1

± 0.2

Description

Belden #9501

Belden #9533

Belden #83503

When used

For 2-wire RTDs and potentiometers. For 3-wire RTDs and potentiometers.

Short runs less than 100 feet and
normal humidity levels.

For 3-wire RTDs and potentiometers.
Long runs greater than 100 feet or
high humidity levels.

Conductors

2, #24 AWG tinned copper (7× 32)

3, #24 AWG tinned copper (7× 32)

3, #24 AWG tinned copper (7× 32)

Shield

Beldfoil aluminum polyester shield
with copper drain wire.

Beldfoil aluminum polyester shield
with copper drain wire.

Beldfoil aluminum polyester shield
with tinned braid shield.

Insulation

PVC

S-R PVC

Teflon

Jacket

Chrome PVC

Chrome PVC

Red teflon

Agency Approvals

NEC Type CM

NEC Type CM

NEC Art-800, Type CMP

Temperature Rating

80°C

80°C

200°C

RTD Type

α

αα

α

(1)

(2)

(3)

(4)

(5)

(6)

(7)

(8)

100

Platinum

0.00385

X

X

X

200

Platinum

0.00385

X

X

X

500

Platinum

0.00385

X

X

X

1000

Platinum

0.00385

X

X

X

100

Platinum

0.03916

X

X

200

Platinum

0.03916

X

X

500

Platinum

0.03916

X

X

1000

Platinum

0.03916

X

X

10

Copper

(9)

0.00426

X

120

Nickel

(10)

0.00618

X

120

Nickel

0.00672

X

604

Nickel Iron

0.00518

X

(1)

α

is the temperature coefficient of resistance which is defined as the resistance change per ohm per °C.

(2) International Electrotechnical Commission Standard 751-1983
(3) German Standard, DIN 43760-1980 and DIN 43760-1987
(4) U.S. Standard D100
(5) Scientific Apparatus Makers Association Standard RC21-4-1966
(6) Japanese Industrial Standard JIS C1604-1981
(7) Japanese Standard JIS C1604-1989
(8) Minco Type ‘NA’ (Nickel) and Minco Type ‘FA’ (Nickel-Iron)

(9) Actual value at 0°C is 9.042

per SAMA standard RC21-4-1966.

(10) Actual value at 0°C is 100

per DIN standard.

ATTENTION

!!!!

We recommend you use
RTDs that conform to the
standards in the table
above. Failure to heed this
caution may result in
reduced accuracy of the
RTD system.