Publication 1746-UM003A-EN-P

Channel Configuration, Data, and Status 4-5

Table 4.1 Channel Configuration Word (O:e.0 through O:e.7) - Bit Definitions

Define

To Select

Make these bit settings in the Channel Configuration Word
15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Input type selection

100 Pt (385)

0

0

0

0

200 Pt (385)

0

0

0

1

500 Pt (385)

0

0

1

0

1000 Pt (385)

0

0

1

1

100 Pt (3916)

0

1

0

0

200 Pt (3916)

0

1

0

1

500 Pt (3916)

0

1

1

0

1000 Pt (3916)

0

1

1

1

10 Cu (426)

(1)

1

0

0

0

120 Ni (618)

(2)

1

0

0

1

120 Ni (672)

1

0

1

0

604 NiFe (518)

1

0

1

1

150

Resistance Input

1

1

0

0

500

Resistance Input

1

1

0

1

1000

Resistance Input

1

1

1

0

3000

Resistance Input

1

1

1

1

Data format selection

Engineering units x 1

(3)

0

0

Engineering units x 10

(4)

0

1

Scaled-for-PID

1

0

proportional counts

1

1

Broken input selection

Set to Zero

0

0

Set to Upscale

0

1

Set to Downscale

1

0

Invalid

1

1

Temperature units
selection

Degrees C

(5)

0

Degrees F

(5)

1

Filter frequency selection 28 Hz

0

0

50/60 Hz

0

1

800 Hz

1

0

6400 Hz

1

1

Channel enable

Channel Disabled

0

Channel Enabled

1

Excitation current
selection

1.0 mA

0

0.25 mA

1

Cal. Disable

Enable

0

Disable

1

Lead R. Enable

Disable

0

0

Periodic

0

1

Always

1

0

Invalid

1

1

(1) Actual value at 0 °C is 9.042

per SAMA standard RC21-4-1966.

(2) Actual value at 0 °C is 100

per DIN standard.

(3) Values are in 0.1 degree /step or 0.1

/step for all resistance input types, except 150

. For the 150

resistance input type, the values are in 0.01

/step.

(4) Values are in 1 degree /step or 1

/step for all resistance input types, except 150

. For the 150

resistance input type, the values are in 0.1

/step.