Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 78

Advertising
background image

Publication 1746-UM003A-EN-P

5-6 Ladder Programming Examples

Figure 5.6 Programming for PID Application

ATTENTION

!!!!

When using the module’s scaled-for-PID data format with
the SLC PID function, ensure that the PID instruction
parameters Maximum Scaled S

max

(word 7) and Minimum

Scaled S

min

(word 8) match the module’s minimum and

maximum scaled range, in engineering units, (e.g. -200°C
to +850°C) for each channel. This allows you to accurately
enter the setpoint in engineering units (°C, °F).

First Pass

S:1

15

MOV

Move
Source

Dest

N10:0
0<
O:3.0
0<

I:3.8

11

PID

PID
Control Block
Process Variable
Control Variable
Control Block Length
Setup Screen

N11:0
I:3.0
N11:23
23

END

Use register N10:0 as configuration word for channel 0.

Entering Address N11:0 allocates elements N11:0 to N11:22 for required Control Block file length of 23 words. The Process
Variable is address I:3.0, which stores the value of input data word 0 (channel 0). Output of the PID instruction is stored at
address N11:23 (Control Variable Address).

0000

0001

0002

Advertising