2-10 Installation and Wiring

Figure 2.2 RTD Connections to Terminal Block

When using a 3-wire configuration, the module compensates for resistance
error due to lead wire length. For example, in a 3-wire configuration, the
module reads the resistance due to the length of one of the wires and assumes
that the resistance of the other wire is equal. If the resistances of the individual
lead wires are much different, an error may exist. The closer the resistance
values are to each other, the greater the amount of error that is eliminated.

2-Wire Interconnection

4-Wire Interconnection

3-Wire Interconnection

Cable Shield (Frame
Ground)

Cable Shield (Frame
Ground)

RTD

RTD

RTD

Return

Return

Return

Belden #9501 Shielded Cable

Sense

Sense

Belden #9533 Shielded Cable or
Belden #83503 Shielded Cable

Belden #9533 Shielded Cable or
Belden #83503 Shielded Cable

Leave One Sensor Wire Open

RTD 0
Sense 0
Return 0
RTD 1
Sense 1
Return 1
RTD 2
Sense 2
Return2

RTD 0
Sense 0
Return 0
RTD 1
Sense 1
Return 1
RTD 2
Sense 2
Return2

RTD 0
Sense 0
Return 0
RTD 1
Sense 1
Return 1
RTD 2
Sense 2
Return2

RTD 0

Sense 0

Return 0

RTD 1

Sense 1

Return 1

RTD 2

Sense 2

Return2

RTD 3

Sense 3

Return 3

RTD 4

Sense 4

Return 4

RTD 5

Sense 5

Return 5

RTD 6

Sense 6

Return 6

RTD 7

Sense 7

Return 7

Add
jumper

Cable Shield (Frame
Ground)

Advertising